Easter Office Closure Notice

Please note that our offices will be closed from April 18th to April 21st for the Easter holidays. We'll be back and ready to assist you on Tuesday, April 22nd. Wishing you and your loved ones a joyful and peaceful Easter!🐣🌷

Pepperl + Fuchs 2 Channel Zener Barrier, ATEX

RS Stock No.: 280-6608Brand: Pepperl + FuchsManufacturers Part No.: Z 960
brand-logo
View all in Zener & Galvanic Barriers

Technical Document

Specifications

Number of Channels

2

Module Type

Zener Barrier

Barrier Type

Zener Barrier

Maximum Voltage

250V

Hazardous Area Certification

ATEX

Safety Current Resistance

64Ω

Maximum Operating Temperature

+60°C

Supply Voltage

10V ac

Maximum Current

203mA

Minimum Operating Temperature

-20°C

Safety Current Maximum

203mA

Safety Voltage Maximum

250 V

Operating Temperature Range

-20 → +60°C

Country of Origin

Indonesia

Product details

Z960 Dual Channel AC Powered

Using a dual channel barrier impedes a direct grounding of the intrinsically safe circuit. The ground is only made in the event of a failure, if the zener diodes conduct. This circuit also suppresses influences of external circuits.,Typical application - thermocouples

Isolation Barriers

Pepperl+Fuchs shunt zener diode barriers are for use as safety interfaces between intrinsically safe and non-intrinsically safe circuits. They are manufactured from Makrolon® and designed to conduct electrical signals - in either direction - between safe and hazardous areas and to limit the amount of energy which can be transferred from a safe to a hazardous area in the event of fault conditions occurring in the safe area. All systems shown are licensed for [EEx ia] IIC Class 1, Div1, Groups A-G

Stock information temporarily unavailable.

€ 214.70

€ 214.70 Each (ex VAT)

€ 255.49

€ 255.49 Each (inc. VAT)

Pepperl + Fuchs 2 Channel Zener Barrier, ATEX

€ 214.70

€ 214.70 Each (ex VAT)

€ 255.49

€ 255.49 Each (inc. VAT)

Pepperl + Fuchs 2 Channel Zener Barrier, ATEX
Stock information temporarily unavailable.

Stock information temporarily unavailable.

Please check again later.

Technical Document

Specifications

Number of Channels

2

Module Type

Zener Barrier

Barrier Type

Zener Barrier

Maximum Voltage

250V

Hazardous Area Certification

ATEX

Safety Current Resistance

64Ω

Maximum Operating Temperature

+60°C

Supply Voltage

10V ac

Maximum Current

203mA

Minimum Operating Temperature

-20°C

Safety Current Maximum

203mA

Safety Voltage Maximum

250 V

Operating Temperature Range

-20 → +60°C

Country of Origin

Indonesia

Product details

Z960 Dual Channel AC Powered

Using a dual channel barrier impedes a direct grounding of the intrinsically safe circuit. The ground is only made in the event of a failure, if the zener diodes conduct. This circuit also suppresses influences of external circuits.,Typical application - thermocouples

Isolation Barriers

Pepperl+Fuchs shunt zener diode barriers are for use as safety interfaces between intrinsically safe and non-intrinsically safe circuits. They are manufactured from Makrolon® and designed to conduct electrical signals - in either direction - between safe and hazardous areas and to limit the amount of energy which can be transferred from a safe to a hazardous area in the event of fault conditions occurring in the safe area. All systems shown are licensed for [EEx ia] IIC Class 1, Div1, Groups A-G